Industrial Remote IO Edge Gateway Data Logger USR-M100
Industrial Remote IO Edge Gateway Data Logger USR-M100
The USR-M100 series controllers are a new generation of IO modules that support data acquisition and control. They adopt an expandable structure design, standard RS485 interface, and come with standard Modbus RTU protocol.
EDGE COMPUTING: Edge acquisition, computing, and automatic reporting
DATA SECURITY: SSL/TLS encryption in TCP client, HTTP client, MQTT
EXTENDABLE IO: 2DO/2DI/2AI, RS485/232, IO Expandable (check option menu)
4G, ETHERNET: 1*WAN, 4G option
Specifications:
Power supply |
|
Input Voltage |
9 – 36 VDC, reverse polarity protection, surge protection |
Power Consumption |
Idle: < 2.4W, Max: < 4.8W |
Serial port |
|
No. |
2 RS485 serial port, the first one can also be RS232 RS232 Terminal block connector: TX, RX RS485 Terminal block connector: A, B |
Baud rates |
600~230400bps |
Data bits |
7,8 |
Stop bits |
1,2 |
Parity |
None, Even, Odd, Mark, Space |
Flow |
None, XON/XOFF |
Physical interface |
|
DI |
2 x Digital non-isolated input (0 - 2 V detected as logic low, 9 - 36 V detected as logic high) |
DO |
2 x Relays DC contacts rating @R(at resistive load)10A / 28V DC AC contacts rating @R(at resistive load)10A / 277V AC,NO AC contacts rating @R(at resistive load)5A /250V AC, NC |
AI |
2 x Analog input 4-20mA |
Extendable I/O modules |
USR-IO4040: 4x Digital input, 4x Digital output USR-IO0440: 4x Analog input(4-20mA), 4x Digital output USR-IO0080: 8x Digital output |
Physical spec |
|
Dimensions (W x H x D) |
79.6x 58 x110 (mm) |
Mounting options |
DIN rail, wall mounting |
Hardware protection |
|
ESD |
IEC61000-4-2, Level 3, class B, contact 6KV, air 8KV |
Surge |
IEC61000-4-5, Level 3, class B |
EFT |
IEC61000-4-4, Level 3, class B |
Status LEDS |
|
Power |
ON: Gateway is powered up OFF: Gateway is not power up |
Work |
When the device is working properly, it blinks for 1s frequency |
NET |
Blinking when the wan connects to internet OFF when there is no work |
DATA |
Blinking when serial port is transmitting data |
DO |
Light on, the channel output is activated |
DI |
Light on, the channel is activated by input signal |
Network |
|
Cellular |
LTE FDD: B1/3/5/7/8/20/28 LTE TDD: B38/40/41 WCDMA: B1/5/8 GSM/GPRS/EDGE: 850/900/1800 |
ETHERNET |
1 x WAN port 10/100 Mbps, compliance IEEE 802.3, IEEE 802.3u standards, supports auto MDI/MDIX |
Software |
|
Network protocols |
ICMP,IPv4,IPv4,ARP,ICMP,TCP,UDP,DHCP,DNS,HTTPS,MQTT,SNMP,Telnet,NTP,SSL v3 |
IP |
DHCP/StaticIP |
Websocket |
Supported |
MQTT |
Supported, standard MQTT protocol, 16 subscription topics and 16 publish topics |
Linkage control |
Supported. Data collection points, DI, and AI can be used as trigger and executed by DO |
IOT PLATFORMS |
Alibaba cloud, AWS IOT, Microsoft Azure, ThingsBoard, IQFLOW, etc. |
User Configuring |
Windows Utility, web console(HTTP) |
Operating environment |
|
Operating temperature |
-40 °C to 75 °C |
Operating humidity |
10% to 90% non-condensing |
Ingress Protection Rating |
IP30 |
MODBUS RTU master |
|
Supported functions |
01, 02, 03, 04 |
Supported data formats |
8 bit: INT, UINT; 16 bit: INT, UINT (MSB first); 32 bit: float, INT, UINT (ABCD (big-endian), DCBA (little-endian), CDAB);64 bit:float |
Supported data points |
128 |